Cooling Tower Modeling ====================== The cooling tower model simulates the removal of heat from the condenser water loop to ambient air by evaporative cooling, and is governed by the following key relationships. Mass continuity ---------------- Assuming no bleed or blow-down, the water mass flow through the tower is conserved: .. math:: \dot{m}_{w,\mathrm{in}} = \dot{m}_{w,\mathrm{out}} = \dot{m}_w Energy balance -------------- The sensible heat removed from the water equals the tower heat duty: .. math:: \dot{m}_w\,c_{p,w}\,(T_{w,\mathrm{in}} - T_{w,\mathrm{out}}) = Q_{\mathrm{tower}} where: - :math:`\dot{m}_w` is the water mass flow rate - :math:`c_{p,w}` is the specific heat capacity of water - :math:`T_{w,\mathrm{in}}` and :math:`T_{w,\mathrm{out}}` are the inlet and outlet water temperatures Overall heat‐transfer model --------------------------- Model the tower as a counter-flow heat exchanger with overall conductance :math:`UA` and log-mean temperature difference :math:`\Delta T_{\mathrm{lm}}`: .. math:: Q_{\mathrm{tower}} = UA \,\Delta T_{\mathrm{lm}} with .. math:: \Delta T_{\mathrm{lm}} = \frac{ (T_{w,\mathrm{out}} - T_{a,\mathrm{in}}) \;-\; (T_{w,\mathrm{in}} - T_{a,\mathrm{out}}) }{ \ln\!\displaystyle\frac{T_{w,\mathrm{out}} - T_{a,\mathrm{in}}} {T_{w,\mathrm{in}} - T_{a,\mathrm{out}}} } where: - :math:`T_{a,\mathrm{in}}` and :math:`T_{a,\mathrm{out}}` are the inlet and outlet air wet-bulb temperatures Evaporative mass loss --------------------- The evaporated water mass flow is tied to the latent heat of vaporization: .. math:: \dot{m}_{\mathrm{evap}} = \frac{Q_{\mathrm{tower}}}{h_{fg}} where :math:`h_{fg}` is the latent heat of vaporization of water. Fan power consumption --------------------- Air is drawn through the tower by a fan against a pressure rise :math:`\Delta p_a`. The electrical power required is: .. math:: P_{\mathrm{fan}} = \frac{\Delta p_a \,\dot V_a}{\eta_{\mathrm{fan}}} where: - :math:`\dot V_a` is the volumetric air flow rate - :math:`\eta_{\mathrm{fan}}` is the fan efficiency Usage in Sustain-LC ------------------- The above equations are implemented in the cooling-tower submodel of the Sustain-LC Gymnasium environment. Users can adjust parameters such as :math:`UA`, :math:`\dot{m}_w`, and fan characteristics to study the impacts on thermal regulation and energy consumption.